First, since the SF6 gas recovery unit is not a simple equipment, it is best to let trained professionals operate it, and relevant personnel need to check whether each connecting part is correctly connected and whether the sealing of each interface is good before use. It can be said that the inspection before use is very important and must be paid enough attention.
Second, for the vacuum pump of SF6 gas recovery unit, we must ensure that it can not be reversed, and the oil level of its components must absolutely meet the requirements. If there is any abnormality during the operation of the device, it needs to be handled by relevant personnel at the same time.
Third, when using the SF6 gas recovery unit to recover gas, you need to start the refrigeration system half an hour in advance. Because a small amount of condensate will be discharged when opening the refrigeration system, these condensate needs to be properly treated.
Fourth, the molecular sieve of SF6 gas recovery unit needs to be replaced when it is used for almost 10000 hours, and the filter element of the filter of the equipment also needs to be replaced in time when it reaches 5000 hours. Wuhan Guodian Xigao Electric Co., Ltd. all rights reserved.